Vane Type Inlet Device: Function, Sizing and Selection Rules
11/09/2026Vane Pack Design and Sizing: Channel Geometry, Drainage and Capacity
11/09/2026Short answer: drift eliminators are selected by the drift loss target, not by the tower size. A conventional cellular eliminator holds drift loss around 0.005% of circulating water; a high efficiency design reaches roughly 0.001%. Whatever the target, the eliminator adds pressure drop to the fan, and a fouled eliminator costs far more in fan power than the drift it saves.
What drift loss actually means
Drift is the water carried out of the tower as droplets, distinct from evaporation. Evaporation is the cooling mechanism and cannot be eliminated; drift is a loss of treated water, a source of plume and a source of chemical deposition on nearby surfaces. Drift loss is normally quoted as a percentage of circulating water flow, and it is the number that decides which eliminator grade is required.
| Eliminator type | Typical drift loss | Pressure drop | Notes |
|---|---|---|---|
| Cellular wave / honeycomb, standard | about 0.005% | 0.05 – 0.1 kPa | Most common; good compromise between drift and fan power |
| Cellular wave, high efficiency | about 0.001% | 0.1 – 0.2 kPa | Used where plume or deposition matters; more sensitive to fouling |
| Blade type, two-pass | 0.002 – 0.005% | 0.05 – 0.15 kPa | Better fouling tolerance, larger footprint |
| Blade type, three-pass | below 0.002% | 0.1 – 0.25 kPa | Higher separation with higher fan penalty |
Pressure drop is the real operating cost
An eliminator pressure drop of 0.15 kPa across a large air flow represents continuous fan power. The comparison that matters at the specification stage is not the drift number in isolation but the drift target against the fan power allowed. A high efficiency eliminator chosen to satisfy a plume requirement can add measurable power consumption over the tower life, and the same requirement is sometimes met more cheaply by controlling dissolved solids in the circulating water.
Fouling is the failure mode that matters
Drift eliminators foul from three directions: biological growth in warm wet passages, calcium carbonate scale where the water is hard, and airborne dust that deposits on the leading edges. Fouling does two harmful things: it raises pressure drop and it distorts the flow path so droplets find a way through. A fouled high efficiency eliminator can perform worse than a clean standard one.
Design decisions that reduce fouling: generous passage size, a wash arrangement that reaches the full face, and materials that do not support biofilm. Where make-up water is hard, scale management in the circulating water is more effective than any eliminator design change.
Materials
PVC and PP are standard for fresh water cooling towers. FRP and stainless are used for high temperature duties, seawater or where fire resistance is required. The material decision is driven by water chemistry and operating temperature, not by drift performance.
What to specify
- Drift loss target as a percentage of circulating water flow, and whether it is driven by plume, deposition or water loss.
- Air flow and face velocity at the eliminator plane.
- Allowable pressure drop and the resulting fan power.
- Water chemistry: hardness, chloride, suspended solids.
- Cleaning method available: online wash, offline manual, or none.
- Temperature and fire resistance requirement.
For the droplet separation logic behind these choices, see Fiberbed vs Wire Mesh Demister, and for pressure drop behaviour in gas service see What Pressure Drop Should You Expect from a Mist Eliminator. Power station applications are summarised on the power industry page.
Send the circulating water flow, air flow, drift loss target, water chemistry and available pressure drop and we will propose an eliminator type with the corresponding fan power penalty.
Frequently Asked Questions
What drift loss should I specify for a cooling tower?
Does a high efficiency eliminator always reduce plume?
Why did pressure drop rise without a flow change?
Which material suits seawater cooling towers?
Worked example: what a drift rate means in litres per hour
Drift figures are quoted as a percentage of circulating water, which makes them hard to judge. Converting to litres per hour shows what actually leaves the tower.
| Step | Calculation | Result |
|---|---|---|
| Circulating water | 3,000 m³/h | — |
| Drift at 0.005% of circulation | 3,000 × 0.00005 | 0.15 m³/h = 150 L/h |
| Drift at 0.001% of circulation | 3,000 × 0.00001 | 0.03 m³/h = 30 L/h |
| Difference over a month of continuous running | (150 − 30) × 24 × 30 | 86,400 L |
The same tower, with the same fill and the same duty, loses an extra 86 cubic metres of water a month at the higher drift rate. That water carries the treatment chemicals and the dissolved solids with it, so the cost is not only make-up water: it is also the chemical dosing that has to be repeated and the plume that the neighbours see.
Worked example: fan power for the eliminator pressure drop
| Step | Calculation | Result |
|---|---|---|
| Air flow through the tower | 200,000 m³/h | 55.6 m³/s |
| Fan power at 10 Pa, fan efficiency 0.70 | 55.6 × 10 / 0.70 / 1000 | 0.79 kW |
| Fan power at 20 Pa, same efficiency | 55.6 × 20 / 0.70 / 1000 | 1.59 kW |
| Extra energy over a year at 8,000 h | (1.59 − 0.79) × 8,000 | 6,400 kWh |
Doubling the eliminator pressure drop costs about 6,400 kWh a year on a tower of this size. That is the number to weigh against the water saved when choosing between a standard and a high efficiency eliminator: the drift reduction is usually worth more than the fan energy, but the comparison is only meaningful when both are expressed in the same units.
Operational troubleshooting
How is drift rate measured on a running cooling tower?
Why does drift eliminator pressure drop rise as the tower fouls?
- Gas-Liquid Separation Fundamentals — terminology, separation mechanisms and internal selection
- Technical Data Sheet — material and performance reference data
- All Technical Articles — complete engineering index
If you are working on a replacement
Most of the work behind an article like this is a replacement inside an existing vessel, where the available dimensions decide more than the nominal duty. See the process data needed to size and select it, the scope from data review through to delivery and what has to be supplied before a price is issued.
More on vane packs and chevron mist eliminators
- Vane Packs and Chevron Mist Eliminators: Essential Equipment for Efficient Gas-Liquid Separation – the guide that covers this device family end to end
- Calming Baffles and Perforated Plates: Flow Distribution Design Rules
- Vane Pack Design and Sizing: Channel Geometry, Drainage and Capacity
- Vane Type Inlet Device: Function, Sizing and Selection Rules
Not sure which technology fits the duty at all? Which Mist Eliminator or Coalescer Do You Need? A Selection Map by Duty compares all four on droplet cut point, pressure drop and fouling tolerance.