Reboiler Mist Eliminators in Ethylene, C3 Splitter Heat Pumps and Refrigeration Chillers

Why a Shorter Kettle Bundle Can Need a Larger Shell: Length, Diameter and Which Area Binds
11/15/2026
Why the Same Demister Duty Gives Different Diameters: Five Conventions That Move the Answer
11/15/2026
Why a Shorter Kettle Bundle Can Need a Larger Shell: Length, Diameter and Which Area Binds
11/15/2026
Why the Same Demister Duty Gives Different Diameters: Five Conventions That Move the Answer
11/15/2026

A reboiler is not a generic vessel with an eliminator bolted on. Between an LNG pre-cooling kettle, an ethylene cold-section reboiler, a C3 splitter heat-pump reboiler and a refrigeration chiller evaporator, the same physical rule applies but the binding constraint changes completely. This page sets out what differs, so that an element recommended for one service is not transplanted into another on the strength of a similar duty.

The rule that does not change

In every one of these services, vapour is generated inside a shell and has to leave through a dome. Three consequences follow in all four cases:

  • The cross-section is set by volumetric vapour flow, not by heat duty. Two units with the same duty but different boiling pressures need very different dome areas.
  • The element area is limited by the shell chord at its installed height, so the level band is a capacity parameter, not just an operating range.
  • Liquid must drain back into the pool without passing counter-current through the gas it was just removed from, otherwise a correctly sized element re-entrains what it captured.

What changes is which of these bites first, and what the failure looks like when it does.

The four services side by side

Service Boiling medium Vapour density Dominant risk Element tendency
LNG pre-cooling kettle propane, 17 C to minus 35 C moderate to high at the warm end, low at the cold end carryover to a large centrifugal compressor; propane inventory mesh plus vane combination in the dome
Ethylene cold-section reboiler ethylene or propylene refrigerant low, cold service fouling and polymer deposition on the media vane preferred; mesh only with irrigation
C3 splitter heat-pump reboiler propane at the column bottoms condition moderate very small temperature approach, high liquid load, liquid to compressor high-capacity vane with generous drainage
Refrigeration chiller evaporator ammonia, propane, propylene or HFO depends entirely on suction temperature icing, oil carryover, and compressor protection mesh where clean, vane where oil fouling is possible

Ethylene cold section: fouling decides the element, not the cut point

In ethylene separation the reboilers sit in a cold section where trace heavies, polymer and tar can deposit on any surface that liquid passes through. A wire mesh has an enormous internal surface and a tortuous path, which makes it an excellent coalescer and a poor choice where deposition is expected: once the bed begins to load with polymer, the drainage channels close, the pressure drop rises and the element starts to re-entrain.

Practical consequences:

  • Prefer vane geometry where fouling is credible. Open channels drain and can be cleaned; the coarser cut point is acceptable because the downstream compressor protection is usually provided by a second stage.
  • If mesh is required for the cut point, design for irrigation from the start. A wash header above the pad, and a drain path that does not rely on the pad being clean, are part of the element specification rather than an afterthought.
  • Watch the level, not the pad. Polymer deposition is often a symptom of a level that is too low, which raises the local boiling film temperature and cooks the heavies onto the tubes and the element.

C3 splitter heat pump: small approach means large vapour flow per degree

A heat-pump reboiler is doing double duty: it boils the column bottoms and it condenses the compressor discharge in the same shell-and-tube body. The economic point of the arrangement is the very small temperature approach, and that has two consequences for the eliminator. First, the required heat transfer area is large, so the bundle and the shell are large. Second, the vapour is generated at a low temperature difference, so the vapour volumetric flow per unit of heat transferred is high, and the dome area requirement is correspondingly high.

The failure mode is severe, because the vapour goes directly to a compressor inlet. A small liquid flow that would be tolerable in a process condenser is not tolerable here:

  • Size the element for the highest vapour rate in the operating envelope, including the high-pressure ratio condition at start of run when the approach is largest.
  • Provide drainage that works at part load. A heat-pump reboiler at 50 per cent load produces much less vapour, so the element velocity falls far below design; the drainage must still function, or liquid accumulates on the element and is released in bursts when the load returns.
  • Do not accept a cut point specification without a liquid load figure. Liquid mass flow per unit area is what floods a vane pack, and it is often omitted from the datasheet while the droplet cut is stated precisely.

Refrigeration evaporators: the density is whatever the suction condition says

In a refrigeration chiller the allowable velocity can differ by a factor of two or three between refrigerant selections at the same cooling duty, because the vapour density at the evaporating temperature differs by that much. A design transplanted from an ammonia chiller to a propane chiller, or from a high-temperature to a low-temperature application, will be wrong at the dome even if the duty is identical.

  • Compute the dome area at the lowest evaporating temperature in the envelope, not at the nominal rating point.
  • Provide oil management before the element. Oil carried from the compressor accumulates in the evaporator, raises the effective boiling point locally and fouls the element; a drain and a return path are part of the separation design.
  • Consider icing at the element edges. Where moisture ingress is possible, the coldest metal in the dome is the element support, and ice there both blocks drainage and sheds into the compressor.

What to put in the datasheet, whatever the service

Line Why it decides the answer
Boiling medium and saturation condition per stage Fixes the vapour density and therefore the volumetric flow
Vapour rate at 100, 110 and 70 per cent load The dome is sized at the top of the envelope, not at the rating point
Liquid mass flow per unit element area Floods a vane long before the droplet cut point becomes the issue
Level band and element installation height Sets the chord-limited area available
Fouling expectation and cleaning method Decides mesh versus vane more often than the cut point does
Consequence of carryover downstream Sets how much margin is justified, and whether a second stage is needed

An element quoted against the first two lines only is a guess. The four below it are what turns a guess into a specification.

Reference

The LNG kettle case and the capacity factors quoted on this site follow Knoepfler et al., LNG2023, paper 3.2.1, whose literature also cites work on C3 splitter heat-pump reboilers as a route to lower energy use and lower CO2 in the same equipment class.

Frequently Asked Questions

Why do reboiler mist eliminators behave differently in different plants?

Because the binding constraint changes. In an LNG propane kettle the load is set by the temperature approach profile along the bundle; in an ethylene reboiler fouling decides the element type; in a heat-pump reboiler the small approach makes the volumetric vapour flow large and the downstream is a compressor inlet; in a refrigeration evaporator the allowable velocity moves with the suction temperature. The same rule applies, but a different part of it limits the design.

Which element suits an ethylene cold-section reboiler?

Usually a vane pack. The cut point is coarser, but open channels drain and can be cleaned, whereas a wire mesh presents a large internal surface that polymer and tar deposits can close. Where the cut point genuinely requires mesh, the element should be specified with irrigation and a drain path that does not depend on the pad being clean.

Why is carryover so costly in a C3 splitter heat-pump reboiler?

Because the vapour goes straight into a compressor inlet. A liquid flow that a process condenser would tolerate is not acceptable there, and the loss of efficiency that motivates the heat pump, a very small temperature approach, also means a high volumetric vapour flow and a large dome requirement. The element has to be sized for the top of the operating envelope, including the start-of-run condition.

What liquid load figure should be given to a supplier?

The liquid mass flow per unit element area, in kg per square metre per hour or the volumetric equivalent. Flooding is a drainage limit set by liquid load, and a vane pack floods well before its droplet cut point becomes the constraint. A datasheet that states only a droplet cut and a velocity is incomplete.

Can the same evaporator design be reused for a different refrigerant?

Not without recomputing the dome. The allowable velocity depends on the vapour density, which changes by a factor of two or three between refrigerants at the same cooling duty and by more across a suction temperature range. The duty can be identical while the required cross-section is not.

What do I check first if an ethylene reboiler starts carrying liquid?

The level and the pad condition, in that order. A low level raises the local boiling film temperature and cooks heavies onto both the tubes and the element, so a fouled element is often a symptom of a level problem rather than a cause. If the level is correct and the pressure drop has risen over months, the media is loaded and the element should be replaced with a geometry that drains.

Why does carryover appear only when a refrigeration chiller is pulled down to its lowest suction temperature?

Because the vapour density falls with the evaporating temperature, so for the same mass flow the volumetric flow rises and the velocity at the element goes up. A chiller that is clean at the rating point can be above its allowable velocity at the coldest condition in the envelope, which is exactly when the compressor is least able to tolerate liquid.

Leave a Reply