Cooling Tower Drift Eliminators: Drift Loss, Pressure Drop and Fouling Control

Vane Type Inlet Device: Function, Sizing and Selection Rules
11/09/2026
Vane Pack Design and Sizing: Channel Geometry, Drainage and Capacity
11/09/2026
Vane Type Inlet Device: Function, Sizing and Selection Rules
11/09/2026
Vane Pack Design and Sizing: Channel Geometry, Drainage and Capacity
11/09/2026

Short answer: drift eliminators are selected by the drift loss target, not by the tower size. A conventional cellular eliminator holds drift loss around 0.005% of circulating water; a high efficiency design reaches roughly 0.001%. Whatever the target, the eliminator adds pressure drop to the fan, and a fouled eliminator costs far more in fan power than the drift it saves.

What drift loss actually means

Drift is the water carried out of the tower as droplets, distinct from evaporation. Evaporation is the cooling mechanism and cannot be eliminated; drift is a loss of treated water, a source of plume and a source of chemical deposition on nearby surfaces. Drift loss is normally quoted as a percentage of circulating water flow, and it is the number that decides which eliminator grade is required.

Eliminator type Typical drift loss Pressure drop Notes
Cellular wave / honeycomb, standard about 0.005% 0.05 – 0.1 kPa Most common; good compromise between drift and fan power
Cellular wave, high efficiency about 0.001% 0.1 – 0.2 kPa Used where plume or deposition matters; more sensitive to fouling
Blade type, two-pass 0.002 – 0.005% 0.05 – 0.15 kPa Better fouling tolerance, larger footprint
Blade type, three-pass below 0.002% 0.1 – 0.25 kPa Higher separation with higher fan penalty

Pressure drop is the real operating cost

An eliminator pressure drop of 0.15 kPa across a large air flow represents continuous fan power. The comparison that matters at the specification stage is not the drift number in isolation but the drift target against the fan power allowed. A high efficiency eliminator chosen to satisfy a plume requirement can add measurable power consumption over the tower life, and the same requirement is sometimes met more cheaply by controlling dissolved solids in the circulating water.

Fouling is the failure mode that matters

Drift eliminators foul from three directions: biological growth in warm wet passages, calcium carbonate scale where the water is hard, and airborne dust that deposits on the leading edges. Fouling does two harmful things: it raises pressure drop and it distorts the flow path so droplets find a way through. A fouled high efficiency eliminator can perform worse than a clean standard one.

Design decisions that reduce fouling: generous passage size, a wash arrangement that reaches the full face, and materials that do not support biofilm. Where make-up water is hard, scale management in the circulating water is more effective than any eliminator design change.

Materials

PVC and PP are standard for fresh water cooling towers. FRP and stainless are used for high temperature duties, seawater or where fire resistance is required. The material decision is driven by water chemistry and operating temperature, not by drift performance.

What to specify

  1. Drift loss target as a percentage of circulating water flow, and whether it is driven by plume, deposition or water loss.
  2. Air flow and face velocity at the eliminator plane.
  3. Allowable pressure drop and the resulting fan power.
  4. Water chemistry: hardness, chloride, suspended solids.
  5. Cleaning method available: online wash, offline manual, or none.
  6. Temperature and fire resistance requirement.

For the droplet separation logic behind these choices, see Fiberbed vs Wire Mesh Demister, and for pressure drop behaviour in gas service see What Pressure Drop Should You Expect from a Mist Eliminator. Power station applications are summarised on the power industry page.

Send the circulating water flow, air flow, drift loss target, water chemistry and available pressure drop and we will propose an eliminator type with the corresponding fan power penalty.

Frequently Asked Questions

What drift loss should I specify for a cooling tower?

Around 0.005% of circulating water flow is the common baseline. About 0.001% is specified where plume, deposition or water conservation is a concern, at the cost of higher pressure drop.

Does a high efficiency eliminator always reduce plume?

Not on its own. Plume depends on the humidity and temperature of the exit air as well as on drift. Reducing drift removes the liquid water contribution but does not change the saturated vapour component.

Why did pressure drop rise without a flow change?

Fouling. Biological growth, scale or dust deposition narrows the passages. Online washing and water chemistry control are the fixes; changing the eliminator does not solve a fouling problem.

Which material suits seawater cooling towers?

FRP, PP and stainless are used for seawater; PVC is common for fresh water. Chloride level and temperature decide the final choice.

Worked example: what a drift rate means in litres per hour

Drift figures are quoted as a percentage of circulating water, which makes them hard to judge. Converting to litres per hour shows what actually leaves the tower.

Step Calculation Result
Circulating water 3,000 m³/h —
Drift at 0.005% of circulation 3,000 × 0.00005 0.15 m³/h = 150 L/h
Drift at 0.001% of circulation 3,000 × 0.00001 0.03 m³/h = 30 L/h
Difference over a month of continuous running (150 − 30) × 24 × 30 86,400 L

The same tower, with the same fill and the same duty, loses an extra 86 cubic metres of water a month at the higher drift rate. That water carries the treatment chemicals and the dissolved solids with it, so the cost is not only make-up water: it is also the chemical dosing that has to be repeated and the plume that the neighbours see.

Worked example: fan power for the eliminator pressure drop

Step Calculation Result
Air flow through the tower 200,000 m³/h 55.6 m³/s
Fan power at 10 Pa, fan efficiency 0.70 55.6 × 10 / 0.70 / 1000 0.79 kW
Fan power at 20 Pa, same efficiency 55.6 × 20 / 0.70 / 1000 1.59 kW
Extra energy over a year at 8,000 h (1.59 − 0.79) × 8,000 6,400 kWh

Doubling the eliminator pressure drop costs about 6,400 kWh a year on a tower of this size. That is the number to weigh against the water saved when choosing between a standard and a high efficiency eliminator: the drift reduction is usually worth more than the fan energy, but the comparison is only meaningful when both are expressed in the same units.

Operational troubleshooting

How is drift rate measured on a running cooling tower?

By sampling the air above the eliminator, or by measuring the water balance of the tower against make-up and evaporation. The paper method is a sensitised slide or a cascade of filters in the plume; the practical method is a controlled tracer with the tower isolated, which also gives the number the specification is written against.

Why does drift eliminator pressure drop rise as the tower fouls?

Because deposits narrow the passages and, more importantly, reduce the drainage capability of the eliminator. Water held in the pack blocks gas path, so pressure drop rises faster than the fouling alone would suggest. That is why washing the eliminator restores both drift performance and fan power at the same time.